HY-IF43DA-EX

Point-type Infrared Flame Detector

> Strong anti-interference ability oriented to industries
> Multiple output interfaces: RS 485 and relay output
> Combine the power wire with the signal wire through two wire
> Window defogging and defrosting function
> Sensor optical path self-test algorithm


  • Specifications
  • Accessories
  • Download
  • Technical Specification

    Type

    3-waveband explosion-proof type

    Spectrum Range

    3.8 μm; 4.3 μm; 5.0 μm

    Sensitivity

    5-level settable

    3-level by default, corresponding to -level in GB 15631-2008

    Response Time

    10 s (alarm delay: 0–30 s settable)

    Maximum Detection Distance

    Ethanol: 45 m@0.3 m× 0.3 m (147.64 ft@0.98 ft× 0.98 ft)

    Heptane: 55 m@0.3 m× 0.3 m (180.45 ft@0.98 ft× 0.98 ft)

    Working Voltage

    DC24V (16V–28V)

    Working Current

    Monitoring current: 70mA

    Alarm current: 80mA

    Defrost: 300mA

    Indicator

    Alarm: Red indicator steady on

    Fault: Red indicator flashes

    Monitoring: Green indicator steady on

    Output Methods

    RS485

    Two-wire

    420mA current-loop output

    Three sets of relay outputs: Fire relays, fault relays and auxiliary relays

    Operation Environment

    Working temperature: –25°C to +75°C (–13°F to +167°F)

    Relative humidity: ≤95% (RH), non-condensing (40°C ± 2°C )(104°F ± 35.6°F)

    Dimensions

    146 mm × 123 mm × 133 mm (5.75" × 4.84" × 5.24")

    330 mm × 231 mm × 183 mm (12.99" × 9.09" × 7.20")(with package)

    Weight

    1.55 kg (3.42 lb) (without installation bracket)

    Explosion-proof Mark

    ExdC T6 Gb/ExtDA21 IP66 T80°C

    Standard

    GB15631-2008; GB3836.1-2010; GB3836.2-2010; GBT 4208-2017; GB12476.1-2013

    Installation